Underfloor heating: what to check first
Wood flooring can be laid over underfloor heating, but only when the system has been commissioned, the screed is dry, and the floor surface can never go above 27°C.
Before fitting
- Check the flooring is suitable for underfloor heating. Most engineered wood flooring is. Some solid wood, wide boards and certain species are not. Check the product instructions.
- Ask for the heating installer's commissioning record. The system should have been brought up gradually to its full operating temperature, held there for several days, then reduced gradually.
- Re-test the screed with a hygrometer after commissioning. It should be 65% RH or below.
- Confirm the system has controls (for example a floor temperature sensor or limited flow temperature) so the floor surface cannot exceed 27°C at any point.
- Check any underlay is suitable for underfloor heating. The combined thermal resistance of underlay and flooring should not normally exceed 0.15 m²K/W.
During and after fitting
- Before and during fitting, and for at least 48 hours afterwards, keep the heating at a low, steady level (around 15–18°C).
- After that, raise the temperature slowly, by no more than about 2°C per day, until normal living temperature is reached.
- At the start of each heating season, bring the heating up slowly in the same way.
- Avoid covering large areas with thick rugs or furniture without legs, which can trap heat and create hot spots.
The surface temperature of a wood floor must never go above 27°C. Higher temperatures dry the wood too much and can cause gaps, splits and lifting.
Most wood floor problems are traced back to site conditions, moisture or installation, not the product. Following this guidance and the instructions supplied with your flooring is the best way to avoid them.
This is general guidance. Always follow the instructions supplied with your flooring. If in doubt, ask your supplier or a qualified fitter before you start.
Back to all guidance